Double Shed
NJREC
| Specification
| Type | Spacing (mm) | Diameter (mm) | Creepage Distance (mm) | Coupling | Mechanical Failing Load (kN) |
|---|---|---|---|---|---|
| U40B | 110 | 175 | 190 | 11 | 40 |
| U70BS | 127 | 255 | 320 | 16 | 70 |
| U70BL | 146 | 255 | 320 | 16 | 70 |
| U100BS | 127 | 255 | 320 | 16 | 100 |
| U100BL | 146 | 255 | 320 | 16 | 100 |
| U120B | 146 | 255 | 320 | 16 | 120 |
| U120BS | 127 | 255 | 320 | 16 | 120 |
| U160BL | 170 | 280 | 400 | 20 | 160 |
| U160BS | 146 | 280 | 400 | 20 | 160 |
| U210B | 170 | 280 | 400 | 20 | 210 |
| U240B | 170 | 280 | 400 | 24 | 240 |
| U300B | 195 | 330 | 490 | 24 | 300 |
| U400B | 205 | 360 | 550 | 28 | 420 |
| U550B | 240 | 380 | 620 | 32 | 550 |
| U70BLP | 146 | 280 | 450 | 16 | 70 |
| U100BLP | 146 | 280 | 450 | 16 | 100 |
| U120BP | 146 | 280 | 450 | 16 | 120 |
| U160BLP | 170 | 320 | 550 | 20 | 160 |
| U160BMP | 155 | 320 | 550 | 20 | 160 |
| U160BSP | 146 | 320 | 550 | 20 | 160 |
| U210BP | 170 | 320 | 550 | 20 | 210 |
| U240BP | 170 | 320 | 550 | 24 | 240 |
| U300BP | 195 | 380 | 690 | 24 | 300 |
| U420BP | 205 | 380 | 620 | 28 | 420 |
| U550BP | 240 | 390 | 710 | 32 | 550 |
NJREC GROUP has already exported to North America, South America, Australia, Southeast Asia, Africa, Europe, and 50 other countries and regions. Transformer bushings and insulators manufactured by NJREC correspond to international quality standards and are available in the market at competitive prices.
| Product Overview
The U70BLD Double-Shed Toughened Glass Insulator is designed for reliable insulation and mechanical support in overhead transmission lines, distribution networks, and high-voltage power systems. Made from toughened glass, this insulator combines stable electrical performance with strong mechanical strength, making it suitable for long-term outdoor operation under changing weather and environmental conditions.
The double-shed profile helps improve pollution resistance by increasing the creepage path and supporting better surface performance in areas exposed to dust, moisture, salt fog, industrial pollution, and other challenging operating environments. Its disc suspension structure allows the insulator to be connected into strings according to different voltage levels and line design requirements.
| Key Features
Double-shed structure: The optimized shed design helps improve performance in polluted or humid environments by extending the creepage distance and reducing the risk of surface flashover.
Toughened glass material: The glass body provides high mechanical strength, stable insulation performance, and easy visual inspection during routine maintenance.
Reliable suspension design: The disc suspension structure is suitable for forming insulator strings in transmission and distribution line systems.
Strong mechanical performance: The product range covers multiple mechanical failing load options, allowing customers to select suitable models according to line tension and project requirements.
Good environmental adaptability: It is suitable for outdoor use in areas with wind, rain, temperature changes, dust, and industrial pollution.
Convenient maintenance: Toughened glass insulators are easy to inspect visually, helping maintenance teams identify damaged units more efficiently.
| Application Areas
U70BLD Double-Shed Toughened Glass Insulators are widely used in high-voltage transmission lines, power distribution systems, substations, railway power systems, and outdoor electrical infrastructure. They are especially suitable for transmission line projects where stable insulation, mechanical reliability, and pollution resistance are important.
Overhead transmission line insulation
Power distribution network construction
Substation incoming and outgoing line systems
Suspension insulator strings for power towers
Polluted, coastal, industrial, or dusty operating areas
New power line construction and existing line replacement projects
| Why Choose Double-Shed Glass Insulators?
Compared with standard shed designs, double-shed glass insulators provide improved surface distance and better adaptability in contaminated environments. This makes them a practical choice for power line projects in coastal regions, industrial zones, mining areas, and locations with frequent dust or humidity.
The toughened glass structure also offers a clear advantage in maintenance. When damage occurs, the condition of the glass unit can usually be identified visually, helping operators arrange timely replacement and reduce hidden risks in line operation.
| Product Advantages
| Advantage | Description |
|---|---|
| High Mechanical Strength | Suitable for overhead line systems requiring stable mechanical load-bearing performance. |
| Excellent Insulation Performance | Designed to provide reliable electrical insulation for high-voltage power transmission. |
| Pollution Resistance | The double-shed design helps improve performance in polluted, humid, or coastal environments. |
| Easy Inspection | The glass body allows easier visual checking during maintenance and line inspection. |
| Wide Application | Applicable to transmission lines, substations, distribution systems, and power infrastructure projects. |
| Custom Selection | Different specifications are available to meet different voltage levels and mechanical load requirements. |
| Selection Guide
When selecting a double-shed toughened glass insulator, customers should consider the line voltage level, mechanical load requirement, pollution level, creepage distance, coupling size, and installation environment. For projects in heavily polluted or coastal areas, models with longer creepage distance are generally preferred to improve insulation reliability.
If you are not sure which model is suitable for your project, you can provide line voltage, installation location, pollution level, mechanical load requirement, and project drawings. NJREC can assist with model selection based on your technical requirements.
| Quality and Inspection
NJREC focuses on product quality, dimensional accuracy, mechanical performance, and stable insulation capability. Each insulator is manufactured to meet power industry requirements and is suitable for international power transmission and distribution projects.
Inspection can include appearance checking, dimensional verification, mechanical performance testing, and electrical performance testing according to project requirements. Test reports and related documents can be provided when required by customers.
| Installation and Maintenance Notes
Check the insulator surface before installation to ensure there are no visible defects or transportation damage.
Confirm that the coupling size and accessories match the power line design requirements.
Install the insulator string according to engineering drawings and relevant power line construction standards.
Carry out regular line inspections, especially after storms, strong wind, lightning, or heavy pollution events.
Replace damaged units in time to ensure safe and stable operation of the power system.


A: T/T and L/C are acceptable, and T/T will be more appreciated. 30% deposit, 70% balance against B/L copy. Or 100% irrevocable L/C at sight.
A: You can provide us with your drawings and specifications, and we will produce according to your drawing. If you do not have a clear plan, we can also design according to your requirements.
A: Standard export packing or customized packing is available as your request.
A: OEM/ODM can be acceptable.
A: Our company has already achieved ISO9001 certification, and we have test reports.
A: Our salesmen will reply to your inquiry within 24 hours. We can provide technical support and other assistance as needed.